A data sheet for an SBS modified bitumen membrane can list a dozen or more properties, each with its own test standard. This guide sets out the main parameters, the methods usually cited, and what each one tells a specifier or buyer. Exact limits vary with product type and must be taken from the manufacturer's data sheet and declaration of performance.
The standards framework
In Europe, reinforced bitumen sheets for roof waterproofing are covered by EN 13707, which defines the characteristics a manufacturer must declare and refers to individual test methods. Sheets for basement tanking and other uses fall under related product standards. In North America, SBS sheets are covered by ASTM material specifications according to reinforcement: D6164 for polyester, D6163 for glass fibre and D6162 for combined polyester and glass. These are material specifications only and do not address the suitability of a particular roof design.
Main parameters and test methods
| Parameter | Typical EN method | What it tells you |
|---|---|---|
| Length, width, straightness | EN 1848-1 | Roll yield and how well the sheet lays straight for even laps |
| Thickness and mass per unit area | EN 1849-1 | Amount of compound; drives durability and handling weight |
| Watertightness | EN 1928 | Resistance to water under pressure |
| Tensile strength and elongation | EN 12311-1 | Load capacity and ability to stretch over moving joints; mainly set by reinforcement |
| Tear resistance (nail shank) | EN 12310-1 | Resistance to tearing at mechanical fixings |
| Joint peel and shear strength | EN 12316-1, EN 12317-1 | Strength of lapped seams |
| Flexibility at low temperature | EN 1109 | Cold bending temperature; key indicator of SBS quality |
| Flow resistance at elevated temperature | EN 1110 | Temperature at which compound starts to slide on a vertical sample |
| Dimensional stability | EN 1107-1 | Shrinkage or growth after heating; affects lap integrity |
| Resistance to impact and static load | EN 12691, EN 12730 | Resistance to puncture from dropped tools and point loads |
| Artificial ageing | EN 1296 (heat), EN 1297 (UV) | How much flexibility and flow resistance are retained over time |
| Granule adhesion | EN 12039 | How well the cap surfacing stays in place |
How to read the numbers together
Cold flexibility and flow resistance
Tensile strength and elongation
Thickness and mass
Declared values are usually minimums or limits with tolerances
Fire performance
Fire performance of a roof is a system property tested on the full build-up (membrane, insulation, deck), not on the sheet alone. Where local regulations require a fire classification, ask for the system test reference that matches your intended build-up.
Compare data sheets only when the same test method and condition (new or aged) are used for each parameter.
Using this in an enquiry
List the parameters that matter for your project, the test method you expect and any minimum values from your design specification. Ask for the product data sheet, declaration of performance where applicable, and the certificate of analysis for the batch supplied. Nuroil provides a CoA with every delivery and can arrange third-party inspection on request; send your list through our quote request form.