Expert article3 min read7 sections

Knowledge centre · Industrial chemicals

Oil and non-condensable gases in ammonia refrigeration systems

Where oil and air come from in an ammonia system, why they reduce efficiency and how plants drain oil and purge non-condensables.

Written by the Nuroil trade desk, Sharjah

On this page · 7 sections
  1. 01Why oil collects in ammonia systems
  2. 02How oil is removed
  3. 03Where non-condensable gases come from
  4. 04Why air matters
  5. 05Purging non-condensables
  6. 06How ammonia quality fits in
  7. 07What to ask your supplier

Even with high-purity ammonia in the system, two unwanted substances build up over time in most industrial ammonia plants: compressor lubricating oil and non-condensable gases, mainly air. Neither is a fault in itself, but both need regular removal. This article explains where they come from, what they do, and how plants deal with them, and how the quality of the ammonia you buy fits in.

Why oil collects in ammonia systems

Compressors in ammonia plants are lubricated with oil, and a small amount is carried out with the discharge gas despite oil separators. Conventional mineral oils used with ammonia are largely immiscible with it and are denser than liquid ammonia. As a result, oil that escapes the separator tends to settle at low points in vessels such as receivers, intercoolers, surge drums and evaporators rather than travelling around the circuit with the refrigerant.

Oil that settles in heat exchangers coats surfaces and reduces heat transfer. In evaporators running at low temperature it becomes thick, which makes it harder to remove. Left alone, accumulated oil can reduce capacity and, in extreme cases, return to compressors in slugs.

How oil is removed

Plants fit oil drain points or oil pots at the bottom of vessels where oil collects. Draining is done periodically under a written procedure. Because ammonia is present with the oil, the drained oil is first allowed to give off its dissolved ammonia to a safe destination, often by warming the oil pot and returning vapour to the low-pressure side, before any oil is released to a container. Oil drained from an ammonia system should not be reused without the oil supplier's guidance.

  • Drain points must be designed for the job, with suitable valves (often including a self-closing valve).
  • Draining is never left unattended and is only carried out by trained staff with PPE.
  • The quantity of oil drained, compared with the amount added to compressors, helps operators spot problems with oil separators.

Where non-condensable gases come from

Non-condensable gases are those that will not condense at the condenser's temperature and pressure. In ammonia plants they are mainly air, which enters:

  • During construction or maintenance, if the system is not fully evacuated before charging or after being opened.
  • Through leaks on the low-pressure side when parts of the system run below atmospheric pressure.
  • In small quantities through charging if hoses and connections are not purged.

Some non-condensables can also form from the slow breakdown of oil or refrigerant at high temperature.

Why air matters

Air collects in the condenser and high-pressure receiver, where it takes up surface area and adds its own partial pressure. The plant then has to condense at a higher pressure, which raises compressor power and reduces capacity. Air also brings moisture with it, adding to the water content of the ammonia.

Purging non-condensables

Automatic purgers draw a sample of gas from purge points at the condenser outlets and receivers, cool it to condense the ammonia, and release the remaining non-condensable gas, usually through a water bubbler that absorbs any residual ammonia. Industry practice favours several purge points, purged one at a time, rather than a single point. Modern purgers can also report how much air they have removed, which helps locate leaks.

Rising condensing pressure without a rise in load or ambient temperature is a classic sign that non-condensables need attention.

How ammonia quality fits in

Refrigeration-grade ammonia is specified with very low oil and water contents precisely so that new charge does not add to these problems. Workplace safety guidance describes refrigerant-grade ammonia as at least 99.95% pure with tight limits on water and oil. Buying a lower grade, or ammonia from containers previously used for other service, can introduce oil and water that the plant then has to remove.

What to ask your supplier

Ask for refrigeration grade with a certificate of analysis that reports ammonia purity, water and oil (non-volatile residue). Confirm the container is dedicated to clean ammonia service. Nuroil provides a CoA with every delivery and can arrange third-party inspection on request. Send your requirements through our quote request form.