Not all anhydrous ammonia is the same. Fertilizer and general industrial grades are perfectly suitable for their own uses, but a refrigeration system needs ammonia with very little water and oil. This article explains what refrigerant grade means, what water does inside a system and what buyers should check before charging a plant.
What refrigerant grade means
Refrigerant-grade anhydrous ammonia is a clear, colourless liquid or gas free of visible impurities. Guidance published by the US occupational safety agency describes it as at least 99.95% ammonia, with water no more than 33 parts per million and oil no more than 2 parts per million. Industry standards for ammonia refrigeration set purity tables for charging ammonia, and some suppliers offer premium grades that meet or exceed those limits. Requirements differ between standards and regions, so the system designer's specification and the current edition of the applicable standard should always be the reference.
| Grade (typical description) | Typical water level | Usual application |
|---|---|---|
| Refrigerant grade | Very low, e.g. 33 ppm maximum in widely cited guidance | Charging and topping up refrigeration systems |
| Some commercial or high-purity industrial grades | Low, in the hundreds of ppm | Chemical processing; check suitability before refrigeration use |
| Industrial or agricultural grade | Higher, often a few tenths of a percent | Fertilizer, emissions control, chemical feedstock |
Water in agricultural and some industrial grades is not always a sign of poor quality. A small water content is deliberately maintained in certain transport tanks because it helps inhibit stress corrosion cracking of the steel. That is fine for those uses but undesirable in a refrigeration circuit.
What water does to a refrigeration system
Ammonia and water are completely miscible, and water does not evaporate with the refrigerant in the evaporators. Instead it accumulates on the low-pressure side, in evaporators, accumulators and low-side vessels, and the concentration rises over time.
- Shifted pressure–temperature relationship. An ammonia–water mixture boils at a higher temperature than pure ammonia at the same pressure. To reach the required evaporating temperature, operators must run at lower suction pressure, which means more compressor work and higher energy use.
- Lost capacity. Diluted refrigerant carries less cooling per unit circulated, so the plant struggles to hold room temperatures.
- Corrosion and oil problems. Ammonia–water solutions are more corrosive than dry ammonia, and water contributes to degraded compressor oil and sludge.
The industry association for ammonia refrigeration has long published guidance on water contamination, covering where water enters, where it concentrates, how to sample and measure it, and equipment for removing it. That guidance has since been folded into the association's standard on system maintenance. Water usually gets in through poor evacuation after maintenance, leaks on parts of the system running below atmospheric pressure, or charging with the wrong grade.
Oil and other impurities
Oil content is limited because oil carried in with the charge collects in evaporators and vessels, coats heat transfer surfaces and must eventually be drained. Oxygen above a few ppm in liquid ammonia can promote stress corrosion cracking in steel, which is one reason systems are evacuated properly before charging and why non-condensable gases are purged in operation.
Good practice when charging
- Confirm the grade on the certificate of analysis matches the specification before the delivery is connected.
- Use clean, dry charging hoses and fittings rated for ammonia; never use copper or brass components.
- Follow the plant's written charging procedure, with trained staff, gas detection working and personal protective equipment in place.
- Record the quantity charged and the batch reference so water content can be traced if problems appear later.
- Test system water content periodically by sampling from the low side, as recommended in industry guidance.
Charging a refrigeration plant with fertilizer-grade ammonia saves little and can cost a great deal in lost capacity and water removal later.
What to ask your supplier for
State "refrigerant-grade anhydrous ammonia" explicitly, along with the purity standard your system was designed to, the quantity and container type (cylinders, ton containers or bulk ISO tanks). Ask for a batch certificate of analysis showing ammonia content, water and oil, the current safety data sheet and container test certificates. Nuroil supplies a CoA with every delivery and can arrange third-party inspection on request for industrial refrigeration customers. Use the quote request form to set out your requirements.