Ammonia is an excellent refrigerant, but it is toxic and corrosive, and a significant release in a cold store or processing plant can injure or kill. This article gives a general, conservative overview of the main safeguards. It is not a substitute for the system designer's documentation, the applicable regulations and standards, or the product safety data sheet, which should always be the primary references.
Know the hazard
- Toxicity. Ammonia severely irritates the eyes, throat and lungs. US occupational limits include a permissible exposure limit of 50 ppm over an eight-hour shift, and a lower recommended limit of 25 ppm with a 35 ppm short-term limit. A concentration of 300 ppm is classed as immediately dangerous to life or health.
- Odour is not a safeguard. Most people smell ammonia at roughly 5 to 50 ppm, but regular workers can become less sensitive to it. Anyone who smells ammonia should leave the area and the cause should be investigated.
- Cold burns. Liquid ammonia boils at about minus 33 °C and can freeze skin and eyes, with alkali burns that continue until the area is flushed with water.
- Flammability. Ammonia burns only in a narrow concentration range of roughly 16 to 25% in air, but in an enclosed room with an ignition source this can cause an explosion.
- How it moves. Ammonia gas is lighter than air and tends to rise, but a release of cold liquid can form an aerosol that stays near the floor.
Gas detection
Fixed ammonia detectors are the first line of defence because they work continuously, regardless of whether anyone is present. Good practice includes:
- Detectors in machinery rooms and in refrigerated spaces near evaporators, valve groups and other likely leak points.
- Low-level alarms that warn staff and start emergency ventilation, and higher-level set points that shut down non-essential electrical equipment in machinery rooms.
- Audible and visual alarms inside and outside the affected area, with signals to a monitored location.
- Regular calibration and functional testing according to the manufacturer's instructions, with records kept.
- Portable detectors for maintenance work and for checking readings at several heights, since gas may collect high and aerosol low.
Exact detector locations and alarm set points must come from the applicable standards and the system designer, not from general articles.
Ventilation
Machinery rooms need continuous ventilation and a separate emergency ventilation system that starts automatically on detection and can be switched on manually from outside the room. The aim is to keep concentrations below dangerous levels and well away from the flammable range. Exhaust should discharge safely away from people and air intakes. Because ammonia dissolves readily in water, water spray or fog is sometimes used by trained responders to knock down vapour, with the run-off then contained.
Personal protective equipment
| Task | Typical protection (confirm with SDS and risk assessment) |
|---|---|
| Routine walk-through, no ammonia odour | Normal work clothing; escape respirator available where required |
| Maintenance, oil draining, line opening | Chemical goggles and face shield or full-face respirator, chemical-resistant gloves and clothing |
| Emergency response or unknown concentration | Self-contained breathing apparatus and appropriate chemical protective suit, by trained responders only |
Respirators must be selected, fitted and maintained under a formal respiratory protection programme. Contact lenses should not be worn where ammonia exposure is possible. Eyewash stations and safety showers should be located close to machinery rooms and work areas and tested regularly.
Procedures and training
- Written procedures for normal operation, oil draining, charging, isolation and lockout before maintenance.
- Permit-to-work for line breaking and other high-risk jobs, including contractor work.
- An emergency action plan with evacuation routes, assembly points, emergency shut-off locations and liaison with local emergency services.
- Regular training and drills so every worker knows the alarms and the evacuation route.
- Larger systems often fall under process safety management rules; in the United States, for example, systems holding 10,000 lb or more of ammonia are covered.
Detection gives the warning, ventilation buys time and trained people make the right decisions. All three are needed.
Supply and documents
When buying ammonia for an existing plant, keep the current safety data sheet on file at the site and make sure it reaches the people who handle deliveries. Specify refrigerant-grade anhydrous ammonia, the container type and the purity standard, and ask for a certificate of analysis with each delivery. Nuroil provides a CoA with every delivery and the SDS on request for industrial refrigeration customers. You can set out your requirements on the quote request form or via contact us.