Walk into the machine room of a large cold store, meat plant, dairy or brewery and the refrigerant is very likely ammonia, designated R717 in refrigerant numbering. It has been used for well over a century and, despite many synthetic alternatives arriving since, it remains the standard choice for large industrial systems. This article explains why, and what the trade-offs are.
Where ammonia systems are found
Ammonia is used wherever a lot of cooling is needed in one place. Typical sites include meat, poultry and fish processing, dairies and ice cream plants, breweries and wineries, juice and soft drink plants, cold storage warehouses, seafood processing on ships and parts of the petrochemical industry. These systems often hold several tonnes of refrigerant and run around the clock.
Thermodynamic efficiency
Ammonia boils at about minus 33 °C at atmospheric pressure and absorbs a large amount of heat as it evaporates. That high latent heat means a given mass of ammonia moves more heat than most alternatives, so less refrigerant has to be circulated for the same duty. Equipment makers describe it as one of the most efficient refrigerants for industrial applications, and its good heat transfer properties allow compact evaporators and condensers. For plants that run continuously, lower energy use over decades is the main economic argument.
Environmental profile
Ammonia is a naturally occurring compound with zero ozone depletion potential and zero global warming potential. That matters because many synthetic refrigerants are being phased down under environmental rules, which affects the long-term cost and availability of refill gas for systems that use them. An ammonia plant designed today is not exposed to those phase-down schedules, which is a strong planning argument for owners of long-lived assets.
Cost and practical advantages
- Low refrigerant cost. Anhydrous ammonia is a high-volume industrial chemical, so charging and topping up a system is relatively inexpensive.
- Self-alarming odour. People can smell ammonia at very low concentrations, often well below harmful levels, so small leaks tend to be noticed early.
- Lighter than air. Ammonia vapour is lighter than air, which helps ventilation design in machinery rooms, although cold releases can behave differently (see below).
- Wide temperature range. The same refrigerant serves blast freezers, cold rooms and process chillers, and ammonia is also used in industrial heat pumps.
The trade-offs
| Advantage | Corresponding drawback or requirement |
|---|---|
| High efficiency and low gas cost | Toxic: exposure must be controlled by design, detection and procedures |
| Zero ODP and GWP | Flammable in a narrow range (around 16 to 25% in air), so ignition sources are managed in machinery rooms |
| Simple, robust steel systems | Attacks copper, zinc and many alloys, so copper piping and fittings cannot be used |
| Odour warns of leaks | Workers can become less sensitive to the smell, so fixed gas detection is still needed |
Because ammonia corrodes copper and brass, especially when moisture is present, ammonia systems are built from steel or stainless steel with compatible seals. That rules out the small copper-piped equipment used for many synthetic refrigerants and is one reason ammonia is concentrated in industrial rather than domestic or light commercial cooling.
Leaks are the central safety issue. Liquid ammonia expands to roughly 850 times its volume as a gas, and a release of cold liquid can form a dense aerosol that stays near the ground before warming and rising. Large systems are therefore subject to process safety rules in many jurisdictions, and are designed and operated to recognised industry standards with gas detection, emergency ventilation, isolation valves and trained staff. Many newer plants also reduce the ammonia charge, for example by keeping it in the machine room and using a secondary coolant such as glycol or carbon dioxide in occupied areas.
Ammonia's efficiency and environmental profile are why industry uses it; its toxicity is why it demands disciplined design, maintenance and training.
Buying ammonia for refrigeration
Refrigeration systems need refrigerant-grade anhydrous ammonia, which has much tighter limits on water and oil than fertilizer or general industrial grades. When enquiring, state the grade required, the applicable purity standard, the quantity and the delivery format (cylinders, ton containers or bulk ISO tanks). Ask for a certificate of analysis showing ammonia content, water and oil, and the current safety data sheet. Nuroil can discuss supply for industrial refrigeration users; set out your specification on the quote request form.