Anhydrous ammonia is sold in several purity grades that look the same in the container but differ in their water, oil and trace impurity contents. For a refrigeration plant, the grade affects long-term efficiency and maintenance. For other users, from fertilizer application to electronics manufacturing, the requirements are very different. This guide sets out the main grades and what distinguishes them.
What "anhydrous" means
Anhydrous simply means "without water", to distinguish liquefied ammonia from aqueous ammonia (ammonia solution), which is ammonia dissolved in water at concentrations typically up to around 25–35%. All the grades below are anhydrous, but they still contain small amounts of water, and the permitted amount is one of the main differences between them.
The main grades
| Grade | Typical ammonia content | Typical uses | Critical parameters |
|---|---|---|---|
| Commercial / agricultural | About 99.5% min | Direct soil application, chemical feedstock, flue gas treatment | Ammonia content, water (often up to about 0.5%) |
| Refrigeration grade | 99.95% or 99.98% min | Industrial refrigeration systems | Water, oil, non-condensable gases |
| Metallurgical / high purity | 99.99% and above | Nitriding, heat treatment atmospheres, laboratories | Water, oil, oxygen, other gases |
| Electronic / ultra-high purity | 99.999% and above | Semiconductor and LED manufacture | Trace metals, moisture and gas impurities at ppm or ppb level |
Exact limits vary between producers and standards, so always compare certificates parameter by parameter rather than by grade name alone.
Refrigeration grade in detail
Refrigeration-grade ammonia is the norm for industrial plants. Workplace safety guidance describes refrigerant-grade ammonia as at least 99.95% pure, with tight limits on water and on oil. Producers typically offer refrigeration grades at 99.95% and 99.98% minimum ammonia, the higher grade carrying a lower maximum water content.
- Water: water in an ammonia system raises the evaporating temperature for a given suction pressure, reducing capacity and efficiency. It can also cause corrosion and, in low-temperature parts, freezing problems.
- Oil (non-volatile residue): oil from the supply chain adds to the oil that plants must already drain from vessels.
- Non-condensable gases: air or inert gas in the delivered ammonia ends up in the condenser and must be purged.
Why not use commercial grade in a refrigeration plant?
Commercial or agricultural ammonia may meet its own specification while still carrying more water and oil than a refrigeration system should receive. Over the life of a large plant with regular top-ups, that adds up. Removing water from an operating system is difficult and often involves taking ammonia out for treatment. Specifying refrigeration grade from the start is cheaper than correcting contamination later.
For refrigeration, the grade name matters less than the certified water and oil figures on the certificate of analysis for your lot.
Higher grades
High-purity and electronic grades are produced with additional purification and delivered in specially prepared cylinders or ISO tanks to keep contamination out. They are rarely needed for refrigeration, and their cost reflects the extra processing and dedicated packaging. Specify them only when a process genuinely requires it.
How purity is tested
Ammonia content is usually determined by measuring the residue left after evaporation of a sample; water and oil are determined on that residue or by specific methods. Sampling liquefied ammonia under pressure needs proper equipment and trained staff. If you need independent verification, arrange it with an inspection company that has suitable sampling cylinders and procedures.
Specifying your grade
State the grade name, minimum ammonia content, maximum water and oil, the container type, and the end use. Ask for a lot-specific certificate of analysis and confirmation that the container is dedicated to the grade supplied. Nuroil provides a CoA with every delivery and can arrange SDS and third-party inspection on request; use the quote request form to send your specification.