  1. 01Key properties for safety
  2. 02Static electricity
  3. 03Storage layout
  4. 04Incompatible materials
  5. 05Exposure and first response
  6. 06Supply-side checks

Ethyl acetate has a reputation as one of the milder industrial solvents, and in terms of toxicity it is. Its fire hazard is a different matter. It gives off flammable vapour at any normal working temperature, and most incidents with it involve ignition during transfer rather than chronic exposure. This guide sets out the main controls for warehouses and plants. It complements, and does not replace, the product SDS and local fire regulations.

Key properties for safety

PropertyTypical valueWhat it means
Flash point (closed cup)about −4 °CFlammable vapour is present above the liquid at any ambient temperature
Flammable range in air2.0% to 11.5% by volumeA small leak in a poorly ventilated room can reach the lower limit
Boiling pointabout 77 °CVolatile; vapour pressure is high at warm ambient temperatures
Vapour densityheavier than airVapour collects in pits, drains and low areas and can travel to an ignition source
Occupational limit (NIOSH REL, OSHA PEL)400 ppm, 8-hour averageThe exposure limit for workers; the lower flammable limit of 2% equals 20,000 ppm, so ventilation for health and for fire safety must both be assessed

Static electricity

Ethyl acetate flowing through hoses, filters and fill pipes can build up static charge, and a spark in a flammable vapour space is enough to ignite it.

  • Bond containers together and earth them before any transfer between metal containers, using purpose-made clamps on bare metal.
  • Keep the earth connection in place for the whole transfer, and check clamp condition regularly.
  • Fill drums from the bottom or with a dip pipe reaching close to the bottom, and avoid free-fall splash filling.
  • Take extra care with plastic containers, which cannot be earthed in the same way; follow the packaging supplier's guidance.
  • Staff should wear antistatic footwear in dispensing areas, and synthetic clothing that sheds charge readily should be avoided.

Storage layout

  • Store drums and IBCs in a dedicated, well-ventilated flammable store or outdoor bunded area, away from heat, direct sun and sources of ignition.
  • Electrical equipment in areas where vapour may be present should be rated for the hazardous zone identified in the site's assessment.
  • Provide spill containment sized for the largest container and keep drains covered or isolated.
  • Keep quantities in workrooms to the minimum needed for the shift, in closed containers.
  • Bulk tanks need flame arresters or pressure-vacuum valves on vents, level monitoring, and secondary containment. A nitrogen blanket both reduces fire risk and keeps moisture out.

Incompatible materials

Keep ethyl acetate away from strong oxidisers, nitrates, strong acids and strong alkalis. Alkalis also hydrolyse the ester. Do not store it in the same compartment as oxidising agents such as concentrated nitric acid or hypochlorites. Ethyl acetate attacks some rubbers and plastics, so check hoses, seals and pump diaphragms for compatibility; PTFE and suitable fluoroelastomers are common seal choices.

Exposure and first response

Vapour irritates the eyes, nose and throat, and high concentrations cause drowsiness and dizziness. Repeated skin contact dries and cracks the skin. Use local exhaust ventilation at open filling points, safety glasses or goggles and chemical-resistant gloves suited to esters, and follow the respirator selection in the SDS where ventilation is not enough. For spills, remove ignition sources, ventilate, absorb with inert material and use non-sparking tools to collect it. Fires are fought with foam, dry chemical or carbon dioxide; water may be ineffective but can cool exposed containers.

Treat every ethyl acetate transfer as a potential ignition event: earth, bond, ventilate and control the flow.

Supply-side checks

Ask your supplier for the current SDS in the language your site uses before the first delivery, and confirm container type, UN marking and labels in advance so your store can receive them. Nuroil provides the SDS on request and a CoA with every delivery. Contact us if you need packaging details before planning storage.

KEEP READING

More from the Knowledge Centre.

STILL HAVE A QUESTION?

Ask the people who trade it every day.

Our trade managers answer technical and commercial questions about grades, specifications, packing and shipping.

LET’S TALK ABOUT YOUR REQUIREMENTS

Your next shipment starts here.

Request a quote