Technical document

· PDF

Tell us who you are and the document downloads straight away. We use these details only to follow up on your requirement.

Samples & documents

What can we send you?

Tick what you need
Request a quote
Guide3 min read6 sections

Knowledge centre · Fuel oil & engines

Sampling and testing fuel oil deliveries

How fuel oil deliveries are sampled, labelled and retained, what the bunker delivery note must show and how testing protects both buyer and supplier.

Written by the Nuroil trade desk, Sharjah

Pencil sketch of ship-to-ship fuel oil transfer
On this page · 6 sections
  1. 01Types of sample
  2. 02How samples should be taken
  3. 03Sample size, sealing and labels
  4. 04The bunker delivery note
  5. 05Testing before use
  6. 06What to agree with your supplier

A fuel oil delivery is only as provable as the samples and paperwork that go with it. If a quality question comes up weeks later, the representative samples taken during delivery and the bunker delivery note are the evidence both sides will rely on. This guide covers the practical steps for marine bunker deliveries, which also make a sound model for industrial fuel oil receipts.

Types of sample

Several samples are usually drawn from the same delivery, each with a different purpose:

  • MARPOL sample. Required under MARPOL Annex VI as evidence of compliance for port state control. It is the only mandatory sample, and only port state or flag state authorities can release it for analysis.
  • Commercial or supplier sample. Kept by the supplier and used if there is a quality dispute between buyer and seller.
  • Ship's or receiver's samples. One retained on board and one sent to a laboratory for analysis before the fuel is used.
  • Surveyor's sample. Taken when an independent surveyor attends.

How samples should be taken

Continuous drip sampling throughout the whole delivery is the preferred method, because it captures a representative portion of all the fuel transferred rather than a single moment. MARPOL guidelines place the sampling point at the receiving ship's inlet manifold, and many marine guides recommend taking all samples there. Industry standard ISO 13739 also covers sampling procedures.

  • Use new, clean containers and flush or clean the sampler before delivery starts.
  • Keep rain, dust and debris out of the sampler during delivery.
  • Representatives of both supplier and receiver should witness sampling and sealing.
  • Complete and seal each container immediately after delivery, before it leaves the sight of either party.

Sample size, sealing and labels

ItemRequirement or good practice
MARPOL sample volumeNot less than 400 ml; samples are commonly 500 to 750 ml
SealTamper-evident seal with a unique number, recorded on the bunker delivery note
Label detailsSampling location and method, delivery date, name of the supplying barge or installation, receiving ship's name and IMO number, seal number, fuel grade, and signatures and names of both representatives
MARPOL sample retentionOn board until the fuel is substantially consumed, and at least 12 months from delivery
Commercial sample retentionCommonly at least 90 days from delivery
Storage of samplesOutside the accommodation, in a cool, sheltered, ventilated place away from direct sun

Labels should be completed in front of both parties and signed only once delivery is complete. Keep a log of all retained samples so they can be found quickly.

The bunker delivery note

MARPOL Annex VI sets out the minimum content of the bunker delivery note (BDN):

  • Name and IMO number of the receiving ship, port, and date delivery began
  • Supplier's name, address and telephone number
  • Product name, quantity in metric tonnes, and density at 15°C
  • Sulphur content in % m/m
  • A signed declaration by the supplier that the fuel meets the applicable sulphur limit and fuel quality requirements

Check the BDN against the ordered specification before delivery starts, and look for errors such as a wrong sulphur figure. The BDN is countersigned by the receiver and kept on board for three years. If no MARPOL sample is provided, sampling is not witnessed or the BDN is not issued properly, issue a written letter of protest to the supplier.

Representative, witnessed, sealed and logged: if a sample fails any of these, it may not settle a dispute.

Testing before use

Ideally, newly delivered fuel should go into empty tanks and not be used until laboratory results confirm it meets the contract. A full laboratory analysis against ISO 8217 checks viscosity, density, water, sediment, catalyst fines, metals and the other parameters in the specification. Portable test kits on board can give an early indication of density, viscosity, water content, pour point and compatibility. Avoid mixing fuels from different deliveries; if it cannot be avoided, run a compatibility test first. Note that routine analysis may not detect every possible contaminant.

What to agree with your supplier

For marine fuel and fuel oil cargoes, agree in advance the sampling point and method, the number of samples, who holds each one, how long they are kept and which laboratory settles disputes. Nuroil provides a certificate of analysis with every delivery and can arrange independent third-party inspection and sampling on request. Discuss your requirements through the contact page.

PRODUCTS IN THIS GUIDE
KEEP READING

More from the Knowledge Centre.

STILL HAVE A QUESTION?

Ask the people who trade it every day.

Our trade managers answer technical and commercial questions about grades, specifications, packing and shipping.

LET’S TALK ABOUT YOUR REQUIREMENTS

Your next shipment starts here.