  1. 01When disinfection is needed
  2. 02The general sequence
  3. 03Working out quantities
  4. 04Precautions
  5. 05Supply points

Calcium hypochlorite, often supplied as granules sold under the generic name high-test hypochlorite (HTH), is the chlorine compound most widely used for disinfecting wells, boreholes and water storage tanks. Its strength of about 65 to 70% available chlorine, its stability as a dry product and its ready solubility make it practical in the field, including in emergencies when liquid bleach is unavailable or has lost strength.

When disinfection is needed

  • After a new well, borehole or tank is constructed.
  • After repairs, pump replacement or any work that opens the system.
  • After flooding or suspected contamination, such as a positive bacteriological test.
  • Before a long-unused tank or pipe is brought back into service.

Guidance prepared for the World Health Organization stresses that chlorination is the final step, not the whole job. Disinfecting a well without first removing the source of contamination gives only temporary protection.

The general sequence

  1. Find and remove the cause. Repair cracked linings and seals, clear debris and divert surface water away from the wellhead or tank.
  2. Clean. Pump out dirty water, scrub tank walls and floors, and remove sediment. Chlorine is consumed by dirt and organic matter, so cleaning first reduces the chlorine needed and improves the result.
  3. Prepare a chlorine solution. Dissolve calcium hypochlorite in a bucket of clean water, let the insoluble residue settle and use the clear liquid.
  4. Dose and distribute. Add the solution so it reaches all wetted surfaces, including the well lining above the water level and the inside of the tank roof, and run taps until a chlorine smell is noticeable.
  5. Hold for the contact time. Leave the system standing for the period set by the applicable guidance.
  6. Flush and test. Flush to waste until the chlorine residual falls to normal drinking levels, then test, and where possible confirm with bacteriological sampling.

Working out quantities

Shock disinfection uses a chlorine concentration much higher than the normal drinking-water residual, and the required concentration and contact time differ between national and agency guidelines, so use the figures from the guidance that applies to you. The arithmetic is the same in every case: calculate the volume of water (for a well, from the diameter and water depth), multiply by the target concentration to get the grams of chlorine needed, and divide by the available chlorine fraction of the product.

StepExample
Water volumeTank holding 10 m³ (10,000 L)
Chlorine per mg/L of target10,000 L x 1 mg/L = 10 g chlorine
Product at 70% available chlorine10 g / 0.70 = about 14.3 g product per mg/L
Product at 65% available chlorine10 g / 0.65 = about 15.4 g product per mg/L

Multiply the last line by the target concentration from your guidance. Allow for product that has been stored a long time, which may be weaker than its label.

Precautions

  • Wear eye protection, gloves and protective clothing; calcium hypochlorite is corrosive and a strong oxidiser.
  • Always add the product to water, never water to the product, and use a clean, dry container used for nothing else.
  • Never mix it with acids, ammonia, other chlorine products, fuels or organic material.
  • Do not work alone inside tanks or enter confined spaces without proper procedures and ventilation.
  • Repeated heavy chlorination of the same well should be avoided; WHO-linked guidance notes it can cause problems in the aquifer and for users, and does not cure ongoing contamination.
  • Strongly chlorinated flush water should not be discharged to streams or fish ponds without dilution or dechlorination where local rules require it.
Clean first, dose second and test last. Chlorine cannot make up for a well or tank that is still letting contamination in.

Supply points

For water-system work, buyers usually ask for calcium hypochlorite meeting a recognised standard for drinking water chemicals, such as AWWA B300 or a national approval, with available chlorine stated on the certificate of analysis. Specify granules for preparing solutions, and packing sized for field use. Nuroil supplies calcium hypochlorite on request; contact us through the contact page or the quote request form.